The T2 breaker family ranges from 15 through 100 amperes. The T2 trip units are non-interchangeable and use the very latest technology in electromagnetic relays for overcurrent trip protection as well as a version with microprocessor-based electronic trip unit. Thermal overload protection is provided by heat sensitive bimetals. State of the art construction in contacts and arcing chambers aid in limiting damaging fault currents through the protected circuits.
- UL 489/ CSA 22.2 Listed
- Thermal-magnetic
- 100% Amperage Rated (Optional)
- Three Poles (Four Pole available upon request)
- 600Δ/347Vac/ 500Vdc (3 pole series)
- 35kA IC @ 480Vac
- 10xIn Magnetic Trip (500A minimum)
- Dimensions 5.12H x 3.54W x 2.76D (in); 2.84(lbs)
PLEASE NOTE THAT IF THE BREAKER HAS A SHUNT TRIP UNIT IT CAN ONLY HAVE 1 C FORM + BELL ALARM AS AN AUX CONTACT MODULE